San Diego · Code Requirements

What San Diego Requires for Mag-Locks & Access Control

In San Diego the fire permit runs through Development Services — not the fire department — and a Fire Alarm Final closes every job. The city's checklist, in plain English.

Order the permit — $495/siteCheck my city — free

The permit, first

San Diego routes this permit differently from every other California city on this list: the fire permit is issued and reviewed by the Development Services Department (DSD) — its Life Safety reviewers — not by the fire department. The vehicle is a DSD Fire Permit, filed standalone or as a Deferred Fire Submittal, alongside the building permit that carries the door hardware. This page covers the egress mag-lock tied into the fire alarm.

DSD's rule, per Information Bulletin 191 §3: fire alarm and dedicated-function plans go to DSD for review and approval before installation (CFC 907.1.1). The submittal is a real set: floor plan with room uses, device locations, and candela ratings; panel (FACU) locations; the power connection; battery and voltage-drop calculations; conductor types and sizes; cut sheets with listing information; and the interface of the fire-safety control functions — including the door lock and card-access release relays. That last line is where the mag-lock lives on a San Diego set.

Everything runs through OpenDSD, the city's online portal — one free account, no in-person visit. One DSD rule shapes the whole job: all corrections must be submitted together. Responses cannot be uploaded discipline by discipline; a partial resubmittal is rejected, so the correction package has to be coordinated as a single set.

The hardware rules CBC §1010.1.9.x

California's electromagnetic-lock section — the §1010.1.9.x family; the exact subsection number shifts with the adopted CBC edition — sets the baseline DSD's reviewers work from:

1Locking hardware is listed — UL 294, and California State Fire Marshal (CSFM) listed.CBC 1010.1.9.x
2The lock is fail-safe — it releases on loss of power.CBC 1010.1.9.x
3The lock releases automatically on fire alarm or sprinkler actuation.CBC 1010.1.9.x
4A manual release device at the door, independent of the electronics.CBC 1010.1.9.x
5Required signage at the door, as the section prescribes.CBC 1010.1.9.x

Delayed-egress devices are a separate configuration: under the Fire-Rescue Department's Quick Reference Guide, they require a permit in fully sprinklered occupancies with smoke detection.

The Fire Alarm Final is not optional IB 137 §IV

Information Bulletin 137 §IV states it without qualification: "a Fire Alarm Final is required for all buildings with fire alarm systems regardless of the number of devices." There is exactly one narrow exception to the plan requirement — a small tenant-improvement scope of 4 or fewer initiating devices and 10 or fewer notification appliances may file on Affidavit DS-163 with no plans. The Final still applies. Inspections are scheduled online through OpenDSD.

What the city charges

San Diego does not publish a mag-lock fee line in the bulletins above, and we won't invent one. City fees are quoted from DSD's schedule for your scope at intake and passed through at cost, with receipts — our service is the flat fee below, and it does not change.

Close-up of an installed electromagnetic lock

The process, run for you

1

Intake

Send the drawings and hardware cutsheets (or just the drawings; we build the packet). Signed authorization + photo ID.

2

Plans to DSD

We build the DSD set: floor plan with devices and candela ratings, panel locations, calcs, conductor schedule, cut sheets — and the door-release relay interface drawn in, not implied.

3

Review & approval

DSD Life Safety reviews and approves before installation. If corrections come, they go back as one coordinated package — DSD accepts nothing less.

4

Fire Permit issues

The DSD Fire Permit and the building permit issue through OpenDSD; we track both records while your crew mobilizes.

5

Install

Your crew installs to the approved set — including the release relays exactly as drawn.

6

Fire Alarm Final

The Final is scheduled through OpenDSD and coordinated — required on every fire alarm building, every device count. Signed-off permit delivered.

$495 per site — covers up to 9 entries

One flat number per project, set by how many entries are controlled — quoted up front, never a meter. One corrections round included; additional rounds are $295 each, quoted in writing before we resubmit. City fees at cost, passed through with receipts.

Entries (doors / openings)Service fee
1–9 entries$495
10–24 entries$795
25–49 entries$1,195
50+ entries$1,695

Optional: $195 plan code-review (before filing) · $195+ cutsheet packet built for you — the add-ons stay flat at every tier.

Why it matters

The Final always comes

Every building with a fire alarm system gets a Fire Alarm Final — regardless of device count. An unreviewed install meets it with no approved set behind it.

Egress violations

A door that doesn't meet the CBC lock section is a life-safety finding against the building — and the correction belongs to the owner.

Occupancy delays

Corrections run as resubmittals and re-tests on the city's schedule, not yours — a tenant improvement or a move-in waits on a door.

Installed properly per the fire code, none of this is your problem. That is the whole service.

Filed today. You never left the job.

Send the drawings and cutsheets — or just the drawings. We run the checklist, the DSD review, the correction package, and the Fire Alarm Final.

Order the permit — $495/siteCheck my city — free

Sources

City of San Diego Development Services — Information Bulletin 137 (Fire Alarm Final, §IV; Affidavit DS-163 small-TI exception) — sandiego.gov · Information Bulletins 191 (§3 — plans to DSD for review and approval before installation) and 506 (Fire Permit / Deferred Fire Submittal) · DSD Technical Bulletin FIRE-9-2, Fire Alarm Control Panels · San Diego Fire-Rescue Department Quick Reference Guide (delayed-egress permit conditions) — sandiego.gov · OpenDSD online permitting and inspection scheduling · California Building Code §1010.1.9.x (electromagnetic locks) and California Fire Code 907.1.1. Requirements summarized from the cited sources as of October 2026; the filed permit is reviewed against the code in force for the job.