The permit, first
Access control in San Jose runs on two tracks. The hardware rides a building permit — the Building Division plan-checks the door hardware schedule. The fire-alarm tie-in rides a San Jose Fire Department fire-protection system permit — filed as a "Fire Alarm System" or "Dedicated Function System" permit with the SJFD Bureau of Fire Prevention. This page covers the egress mag-lock tied into the fire alarm — the case that pulls both tracks.
The SJFD rule is stated up front in its requirements: no installation or alteration before plan approval and permit issuance (SJFD requirements §1.7).
Plans themselves move electronically: SJePlans is the city's plan-review portal (Building, Planning, Fire, and Public Works all review there), and SJPermits.org carries the applications, fees, inspections, and status. Building Division submittal is electronic only — no hard copies. The SJFD fire permit application is its own form, filed with the fees, and it asks for three numbers an out-of-town contractor has to have ready first: a San Jose city business license number, a workers' comp number, and a CSLB license number. Owners link the property to their account by APN and legal owner name before applying.
Mag-locks on doors that are not in the means of egress are a different, smaller filing — the CBC lock rules below apply to egress doors; non-egress hardware files under the building/electrical permit only.
The hardware rules CBC §1010.1.9.x
California's electromagnetic-lock section — the §1010.1.9.x family; the exact subsection number shifts with the adopted CBC edition — sets the baseline every San Jose reviewer works from:
On the plans, that becomes paper: the Building Division wants the door hardware schedule showing the UL 294 / CSFM listing; SJFD wants the full plan set plus a device table — manufacturer, model, CSFM listing number, and quantity for every device on the fire permit application.
Delayed egress is its own rule SJ PLAN REVIEW NOTE #25
San Jose's published note on security doors covers delayed-egress locks — a stricter, separate configuration, not the plain mag-lock rule. Under Plan Review Note #25 (2019 CBC 1010.1.9.8), a delayed-egress path runs through an approved AMMC arrangement with an adjacent compliant exit door, and the lock must auto-unlock on sprinkler or smoke activation, on loss of power, and from a Knox manual release — with emergency lighting on the path. If your door set includes a delayed-egress lock, it is reviewed under this note, not the standard track.
The fire inspection is a witnessed test SJFD REQS §4.0
SJFD does not sign off on paper. Before the inspection, the contractor completes the NFPA 72 Record of Completion and a full system test (SJFD requirements §4.0 / §4.7 / §4.10). At the inspection itself, the inspector witnesses the device testing — the locks' release behavior is demonstrated, not described. And there is no final without the paperwork behind the system: a central-station certificate is required before final approval (§4.12.1).
What the city charges
The SJFD fire permit application is filed with its fees — the permit does not start moving on a promise to pay later. Beyond that, the city does not publish a mag-lock fee line we can quote you here, and we won't invent one: city fees are the city's, billed at cost and passed through with receipts. Our service is the flat fee below — the number that does not change.
The process, run for you
Intake
Send the drawings and hardware cutsheets (or just the drawings; we build the packet). Signed authorization + photo ID — and we sort the San Jose business license and APN linking before anything files.
Plans & device table
We check the set against the CBC lock rules, build the door hardware schedule, and build SJFD's device table — manufacturer, model, CSFM listing number, quantity.
Two reviews
Building Division plan check on the hardware; SJFD plan approval on the fire side through SJePlans. Nothing installs before approval — that is §1.7, and we file to it.
Permits issue
The building permit and the SJFD fire-protection system permit issue; the record is tracked on SJPermits while your crew mobilizes.
Install & full test
Your crew installs to the approved set, completes the NFPA 72 Record of Completion and the full system test, and the central-station certificate is in hand.
SJFD inspection
The witnessed device test with SJFD — locks release on alarm and on power loss, demonstrated live. Signed-off permit delivered.
One flat number per project, set by how many entries are controlled — quoted up front, never a meter. One corrections round included; additional rounds are $295 each, quoted in writing before we resubmit. City fees at cost, passed through with receipts.
| Entries (doors / openings) | Service fee |
|---|---|
| 1–9 entries | $495 |
| 10–24 entries | $795 |
| 25–49 entries | $1,195 |
| 50+ entries | $1,695 |
Optional: $195 plan code-review (before filing) · $195+ cutsheet packet built for you — the add-ons stay flat at every tier.
Why it matters
Witnessed finals
The SJFD inspection is a live device test. An install that was never reviewed gets measured there — against the approved plans it doesn't have.
Egress violations
A door that doesn't meet the CBC lock section is a life-safety finding against the building — and the correction belongs to the owner.
Occupancy delays
Corrections run as resubmittals and re-tests on the city's schedule, not yours — a tenant improvement or a move-in waits on a door.
Installed properly per the fire code, none of this is your problem. That is the whole service.
Filed today. You never left the job.
Send the drawings and cutsheets — or just the drawings. We run the checklist, both filings, both reviews, and the witnessed inspection.
Order the permit — $495/siteCheck my city — freeSources
San Jose Fire Department fire-protection system requirements (§1.7 plan approval before installation; §4.0–§4.12 inspection, Record of Completion, and central-station certificate) — sanjoseca.gov · SJFD Fire Protection and Special Systems Permit Application — sanjoseca.gov · San Jose Plan Review Note #25, Security Doors Equipped with Special Delayed Egress Locks — sanjoseca.gov · California Building Code §1010.1.9.x (electromagnetic locks) · City of San Jose SJPermits / SJePlans portal guidance. Requirements summarized from the cited sources as of October 2026; the filed permit is reviewed against the code in force for the job.
PermitsPros Comm Inc · City of Concord Business License No. 5027635 · We file permits. We never promise approvals — that's the city's call, and we tell you so up front. Back to Access Control & Mag-Lock Permits.